Tel: 0113 248 9966

Home of the UK's widest range of PAT Tester Equipment

Basket (0)
Home  » PAT Testers » Seaward Apollo 500 PAT Tester

Seaward Apollo 500 PAT Tester

Comprehensive range of tests with built in Risk Assessment Feature

The Apollo 500 is brand new intuitive downloading PAT Testing device from Seaward that combines ease of use with a wide selection of high specification features. The Apollo 500 is built with demanding PAT Testers in mind and is designed to speed up general testing on 230V, 110V appliances and IT equipment.

 

  • Plug and Play technology – Easy to navigate menu system designed to speed up testing.
  • Small lightweight PAT Tester - Designed to fit comfortably in the users hands
  • Advanced memory – Store up to 10,000 assets and download them via USB or wirelessly via Bluetooth.
  • Point to point testing on fixed appliances
  • QWERTY keyboard – Responsive keyboard with recognisable function buttons for fast record editing.
  • Test with complete compliance with the IET Code of Practice 4th Edition
  • Risk Assessment Tool – Enter the environment details and the Apollo 500 will recommend a retest date based on the equipment type and the environmental risks.

 

A main advantage to the Apollo 500 is the introduction of a Risk based assessment tool. The tool is based on the latest IET Code of Practice and allows users to calculate individual re-test dates based on the risk associated with using each appliance. Alongside this feature the tester will perform a series of high end  tests in accordance with the latest edition of the IET Code of Practice 4th Edition and the guidelines introduced by HSE ( Health and Safety Executive )

 

Seaward continue their high reputation and have produced a small, lightweight tester that is easy to carry around. The tester is downloadable so you don't have to keep writing out PAT certificates during your working day. The Apollo 500 can fit comfortably within the user’s hands allowing for one handed testing which can now be performed with ease. Despite the small size the tester comes complete with a full QWERTY keypad featuring five recognisable function buttons and a large high definition colour display. The large backlit display will benefit anyone who wishes to regularly perform and track complex tests in their entirety.

 

The Apollo 500 matches design with functionality by storing 10,000 results along with USB and Bluetooth download and upload compatibility. The tester is designed to be used with Seaward PATGuard 3 software which allows a user to keep track of test history and produce PAT certificates and detailed risk assessment reports. PATGuard 3 is now compatible with PC, tablets and Smartphones.

 

Simple menu systems help you easily navigate to mains powered tests such as Touch Current, Earth Leakage or RCD Trip Time tests. The tester is even versatile enough to test 3 phase equipment and perform point to point testing on fixed appliances. This versalite tester can test off battieres or mains power ensuring you are never slowed down on larger jobs.

 

The Seaward Apollo 500 PAT Tester has several recommended accessories including the Seaward Bluetooth Test and Tag Elite Printer and Seaward Bluetooth Scanner which are available to speed up the asset labelling and the recognition process.

 

The Seaward Apollo 500 PAT Tester is a fast innovative Tester for users looking for versatility combined with simplicity. 

Earth Continuity

  • Test Current: +/- 200mA DC
  • Display Range: 0.01 – 19.99Ω
  • Pass Value: User Defined

Insulation Resistance

  • Test Voltage: 500V / 250V DC @ 1mA nominal
  • Display Range: 0.01MΩ - 19.99MΩ
  • Pass Value: User Defined

IEC Lead Test

  • Test voltage: 5V ac nominal
  • Test: Live / Neutral Checks for o/c, s/c and crossed

Protective Conductor Current/Load

  • Test Voltage: Supply voltage, maximum load current 16A
  • Display Ranges: 0.01mA to 19.99mA
  • Pass Value: User Defined

Touch Current

  • Test Voltage: Supply Voltage, maximum load current 16A
  • Display Range: 0.00 – 3.50mA
  • Pass Value: User defined

Load Power/Current

  • Test Voltage: Supply Voltage, maximum load current 16A
  • Test Duration: Programmable up to a maximum of 255s depending on load. i.e. max duration is reduced for high loads.
  • Display Range: 0.00kVA – 4.00kVA 0.00A – 16.00A

Alternative Leakage Current

  • Test Voltages: >25Vac <50Vac
  • Display Range: 0.00mA to 19.99mA
  • Pass Value: User Defined

RCD Test

  • Test Voltage: 230V +10%,-15%
  • Test Current: 30mA / 150mA rms sinusoidal
  • Display Range: 0ms - 2000ms (30mA), 0-40ms (150mA)
  • Test method: Internal isolation to avoid tripping distribution board RCD

Power Socket Test

  • Voltage Range: 207V – 253V AC Indicates configuration of voltage potential:- Line potential phase to earth, Line potential phase to neutral, Line potential neutral to earth

General

  • Memory size 10,000 records
  • Weight 1.5kg
  • Dimensions 230mm x 150mm x 100mm
  • Power Source Mains or Rechargeable battery pack

  • Seaward Apollo 500 PAT Tester
  • Apollo Calibration Checkbox
  • UKAS Calibration Certificate
  • 2 Year Warranty (requires product registration)
  • Quick Start Guide
  • 30 Day Free Trial of PATGuard 3 Software
  • Mains Power Lead
  • 2 x Test Leads with Probes/Croc Clips
  • 0.5m IEC Lead
  • USB Download Cable
  • Carry Case

  • Related Products